0 SunGrow SGXX series Registerlist

Device Description File



Profile

INDEX NAME DIRECTION REGISTER COUNT FUNCTION TYP CONVERTION ENUMS UNIT
0 nominal_output_power READ 5001 2 fc4 ui16 x/10 kW
1 output_type READ d1 ui16 0/1/2 2-phase (5019 and 5022 are valid)/5019 to 5021 are "Phase x voltage"/ 5019 to 5021 are "x-x line voltage
2 dc_voltage_1 READ 5011 8 fc4 ui16 x/10 V
3 dc_current_1 READ d2 ui16 x/10 A
4 dc_voltage_2 READ d2 ui16 x/10 V
5 dc_current_2 READ d2 ui16 x/10 A
6 dc_voltage_3 READ 4 fc4 ui16 x/10 V
7 dc_current_3 READ d6 ui16 x/10 A
8 total_dc_power READ 5017 2 fc4 ui32 x/10 kW
9 phase_A_voltage READ 5019 6 fc4 ui16 x/10 V
10 phase_B_voltage READ d9 ui16 x/10 V
11 phase_C_voltage READ d9 ui16 x/10 V
12 total_active_power READ 5031 4 fc4 ui32 x/1000 kW
13 total_reactive_power READ d12 si32 var
14 power_factor READ 5035 6 fc4 si16 x/1000
15 grid_frequency READ d14 ui16 x/10 Hz
16 work_state READ d14 ui16 0x0000/0x8000/0x1300/0x1500/0x1400/0x1200/0x1600/0x9100/0x8100/0x8200/0x5500/0x2500 Run/Stop/Key stop/Emergency stop/Standby/Starting/Alarm run/Derating run/Dispatch run/Fault run/Communicate fault