DEVICE DB Login

General parameter

General Modbus-parameter

Note


Documents

0 Mitsubishi Electric M/P/S series, Mr Slim & City Multi Registertable

Device Description File



Profile

INDEX NAME DIRECTION REGISTER COUNT FUNCTION TYP CONVERTION ENUMS UNIT
0 system_on/off READ & WRITE 40025 2 fc3/fc16 ui16 0: off, 1: on, 2: emergency run, 3. test run
1 operating_mode READ & WRITE 40027 2 fc3/fc16 ui16 0: normal, 1: eco
2 set_tank_temperature READ & WRITE 40031 2 fc3/fc16 ui16 x*100 °C
3 status_heating READ 40072 2 fc4 ui16 0: no type, 1: H C1, 2: H C2, 3: H C3 (applicable unit type FTC4) ; 0: no type, 1: H/C A1, H/C B1, H/C C1 (applicable unit type FTC5&6
4 temperature_setpoint_zone1 READ 40082 2 fc4 ui16 x*100 °C
5 temperature_setpoint_zone2 READ 40085 2 fc4 ui16 x*100 °C
6 flow_temperature_setpoint_zone1 READ 40086 2 fc4 ui16 x*100 °C
7 flow_temperature_setpoint_zone2 READ 40088 2 fc4 ui16 x*100 °C
8 room_temperature_zone1 READ 40094 2 fc4 ui16 x*100 °C
9 room_temperature_zone2 READ 40096 2 fc4 ui16 x*100 °C
10 outdoor_ambient_temperature READ 40100 2 fc4 ui16 x*10 0x0000 = 0.0ºC ... 0x036B = 87.5ºC
11 tank_water_temperature READ 40106 2 fc4 ui16 x*100 °C
12 flow_temperature_zone1 READ 40108 2 fc4 ui16 x*100 °C
13 flow_temperature_zone2 READ 40112 2 fc4 ui16 x*100 °C
14 return_temperature_zone1 READ 40110 2 fc4 ui16 x*100 °C
15 return_temperature_zone2 READ 40114 2 fc4 ui16 x*100 °C
16 boiler_flow_temperature READ 40116 2 fc4 ui16 x*100 °C
17 boiler_return_temperature READ 40118 2 fc4 ui16 x*100 °C
18 input_temperature_setpoint_zone1 READ 30041 2 fc4 ui16 x*100 °C
19 input_temperature_setpoint_zone2 READ 30043 2 fc4 ui16 x*100 °C
20 input_flow_temperature_setpoint_zone1 READ 30045 2 fc4 ui16 x*100 °C
21 input_flow_temperature_setpoint_zone2 READ 30047 2 fc4 ui16 x*100 °C
22 input_room_temperature_zone1 READ 30053 2 fc4 ui16 x*100 °C
23 input_room_temperature_zone2 READ 30055 2 fc4 ui16 x*100 °C
24 input_outdoor_ambient_temperature READ 30059 2 fc4 ui16 x*10 0x0000 = 0.0ºC ... 0x036B = 87.5ºC
25 input_flow_temperature READ 30061 2 fc4 ui16 x*100 °C
26 input_return_temperature READ 30063 2 fc4 ui16 x*100 °C
27 input_outdoor_ambient_temperature READ 30059 2 fc4 ui16 x*10 0x0000 = 0.0ºC ... 0x036B = 87.5ºC
28 input_tank_water_temperature READ 30065 2 fc4 ui16 x*100 °C
29 input_boiler_flow_temperature READ 30075 2 fc4 ui16 x*100 °C
30 input_boiler_return_temperature READ 30077 2 fc4 ui16 x*100 °C
31 H/C_control_type READ 30144 2 fc4 ui16 0: heating, 1: cooling