DEVICE DB Login

General parameter

General Modbus-parameter

Note


Documents

0 Victron Energy AC-Coupled PV Inverter Registerlist

Device Description File



Profile

INDEX NAME DIRECTION REGISTER COUNT FUNCTION TYP CONVERTION ENUMS UNIT
0 grid_power_L1 READ 2600 1 fc4 int16 x/1000 kW
1 grid_power_L2 READ 2601 1 fc4 int16 x/1000 kW
2 grid_power_L3 READ 2602 1 fc4 int16 x/1000 kW
3 state_of_charge READ 266 1 fc4 ui16 x/100 %
4 battery_power READ 258 1 fc4 int16 x/1000 kW
5 discharged_energy READ 301 1 fc4 ui16 x/10 kWh
6 charged_energy READ 302 1 fc4 ui16 x/10 kWh
7 energy_from_net READ 2634 2 fc4 ui32 x/100 kWh
8 energy_to_net READ 2636 2 fc4 ui32 x/100 kWh
9 total_power READ 1052 2 fc4 int32 kW