DEVICE DB Login

General parameter

General Modbus-parameter

Note


Documents

0 Belimo Flow sensor datasheet
0 Belimo Flow sensor registerlist

Device Description File



Profile

INDEX NAME DIRECTION REGISTER COUNT FUNCTION TYP CONVERTION ENUMS UNIT
0 relative_volumatric_flow READ 7 6 fc3 ui16 x/100 %
1 absolute_volumatric_flow READ d0 ui16 x/100 l/s
2 absolute_volumatric_flow_in_selected_units_lowword READ d0 ui16 x/1000 UnitSel
3 sensor_value_1 READ d0 ui16 mV|0/1
4 temperature READ 22 2 fc3 ui16 x/100 °C
5 glycol_cincentration READ 26 1 fc3 ui16 x/100 %
6 total_volume READ 60 6 fc3 ui16 x/100
7 total_volume_in_selected_units_lowword READ d9 ui16 UnitSel
8 total_volume_in_selected_units_highword READ d9 ui16 UnitSel
9 bus_termination READ 100 5 fc3 ui16 0/1 disabled/enabled
10 series_number_1st_part READ d15 ui16
11 series_number_2nd_part READ d15 ui16
12 series_number_4th_part READ d15 ui16
13 malfunction_and_service_information READ d15 ui16 0/1/2/3/4/5/6/7/8/9/10/11/12 :-/-/-/reverse flow/-/-/flow actual exceeds fs/flow measurement error/-/flowbody temperature error/communication to sensor interrupted/freeze warning/glycol detected
14 fs(full_scale,max_flow) READ 111 3 fc3 ui16 x/100 l/s
15 fs(full_scale,max_flow)_in_selected_unit_lowword READ d20 ui16 x/1000 UnitSel
16 fs(full_scale,max_flow)_in_selected_unit_highword READ d20 ui16 x/1000 UnitSel
17 sensor_1_typ READ & WRITE 121 1 fc3/fc16 ui16 0/1/2/3/4 none/active/-/-/switch
18 unit_selection_flow READ & WRITE 148 1 fc3/fc16 ui16 0/1/2/3/4/5/6 m³/s|m³/h|l/s|l/min|l/h|gpm|cfm
19 unit_selection_volume READ & WRITE 150 1 fc3/fc16 ui16 0/1/2/3 m³/litre/gallon/cf