0 Mitsubishi Electric ME-AC-MBS-1 User manual

Device Description File



Profile

INDEX NAME DIRECTION REGISTER COUNT FUNCTION TYP CONVERTION ENUMS UNIT
0 AC_unit_on/off READ & WRITE 0 2 fc3/fc16 ui16 0: off, 1: on
1 AC_unit_mode READ & WRITE 1 2 fc3/fc16 ui16 0: auto, 1: heat, 2: dry, 3: fan, 4: cool
2 AC_unit_fan_speed READ & WRITE 2 2 fc3/fc16 ui16 0: auto, 1: low, 2: mid-1, 3: mid-2, 4: high
3 AC_unit_vane_position READ & WRITE 3 2 fc3/fc16 ui16 0: auto, 1: horizontal, 2: pos2, 3: pos3, 4: pos4, 5. vertical, 6: swing
4 AC_unit_temperature_setpoint READ & WRITE 4 2 fc3/fc16 ui16 16…32°C, 60…90°F
5 AC_unit_ambient_temperature READ 5 2 fc4 ui16 10…38°C, 50…100°F
6 window_contact READ & WRITE 6 2 fc3/fc16 ui16 0: closed, 1: open
7 device_disablement READ & WRITE 7 2 fc3/fc16 ui16 0: enabled, 1: disabled
8 IR_remote_command_disablement READ & WRITE 8 2 fc3/fc16 ui16 0: enabled, 1: disabled
9 AC_unit_operation_time READ & WRITE 9 2 fc3/fc16 ui16 0…65535h (time the AC unit is on)
10 AC_unit_alarm_status READ 10 2 fc4 ui16 0: no alarm, 1: alarm
11 indoor_ambient_temperature READ & WRITE 22 2 fc3/fc16 ui16 °C/x10°C/°F (-32768 initialization value)
12 AC_setpoint_temperature READ & WRITE 23 2 fc3/fc16 ui16 16…32°C, 60…90°F