General parameter

General Modbus-parameter

Note


Documents

Carlo Gavazzi Em 24 Registerlist
Carlo Gavazzi EM24 Datasheet
Carlo Gavazzi EM24 Instruction sheet
Carlo Gavazzi EM24 User guide

Device Description File



Profile

INDEX NAME DIRECTION REGISTER COUNT FUNCTION TYP CONVERTION ENUMS UNIT
0 V_L1-N READ 300001/0000h 6 fc4 si32 x/10 V
1 V_L2-N READ d0 si32 x/10 V
2 V_L3-N READ d0 si32 x/10 V
3 V_L1-L2 READ 300007/0006h 6 fc4 si32 x/10 V
4 V_L2-L3 READ d3 si32 x/10 V
5 V_L3-L1 READ d3 si32 x/10 V
6 A_L1 READ 300013/000Ch 6 fc4 si32 x/1000 A
7 A_L2 READ d6 si32 x/1000 A
8 A_L3 READ d6 si32 x/1000 A
9 W_L1 READ 300019/0012h 8 fc4 si32 x/10 W
10 W_L2 READ d9 si32 x/10 W
11 W_L3 READ d9 si32 x/10 W
12 W_summe READ d9 si32 x/10 W
13 Hz READ 300052/0033h 1 fc4 ui16 x/10 Hz
14 KWh(+)_TOT READ 300053/0034h 2 fc4 si32 x/10 kWh
15 KWh(-)_TOT READ 300079/004Eh 2 fc4 si32 x/10 kWh
16 PF_summe READ 300050/0031h 1 fc4 si16 x/1000 pF