0 ÖkoFEN Pellematic Condens series Registerlist

Device Description File



Profile

INDEX NAME DIRECTION REGISTER COUNT FUNCTION TYP CONVERTION ENUMS UNIT
0 ambient_temp READ 2 2 fc4 ui16 x/10 °C
1 HC_mode READ & WRITE 11 2 fc3/fc16 ui16 0: off, 1: auto, 2: heat, 3: setback
2 HC_heating_temp READ & WRITE 12 2 fc3/fc16 ui16 x/10 °C
3 HC_setback_temp READ & WRITE 13 2 fc3/fc16 ui16 x/10 °C
4 HC_remote_control_override READ 14 2 fc4 ui16 x/10 °C
5 HC_current_room_set_temp READ 19 2 fc4 ui16 x/10 °C
6 HC_current_room_temp READ 20 2 fc4 ui16 x/10 °C
7 HC_current_flow_temp_set READ 21 2 fc4 ui16 x/10 °C
8 HC_current_flow_temp READ 22 2 fc4 ui16 x/10 °C
9 HC_pump READ 23 2 fc4 ui16 0: off, 1: on
10 HC_solar_heating_mode READ & WRITE 24 2 fc3/fc16 ui16 0: off, 1: eco, 2: on
11 HC_solar_heating_temp READ & WRITE 25 2 fc3/fc16 ui16 x/10 °C