General parameter

General Modbus-parameter

Note


Documents

Daikin RTD-NET Installationsanleitung

Device Description File



Profile

INDEX NAME DIRECTION REGISTER COUNT FUNCTION TYP CONVERTION ENUMS UNIT
0 setpoint READ & WRITE 1 1 fc3/fc16 ui16
1 fanspeed READ & WRITE 2 1 fc3/fc16 ui16 1|2|3 low|high|high2
2 mode READ & WRITE 3 1 fc3/fc16 ui16 0/1/2/3/4 auto/heating/ventilator/cooling/drying
3 slat READ & WRITE 4 1 fc3/fc16 ui16 1/2/3/4/5/6/7 sway/0°/20°/45°/70°/90°/-
4 on/off READ & WRITE 5 1 fc3/fc16 ui16 0/1 off/on
5 rc_operation_mode READ 51 1 fc4 ui16 0/1/2/3 idle,ventilator/heating/cooling/heating and cooling
6 unit_count READ 20 7 fc4 ui16
7 is_fault READ d6 ui16 0/1 no fault/at least one device has one disturbance
8 fault_code READ d6 ui16
9 return_air READ d6 ui16 x/100 °C
10 filter_alarm READ d6 ui16 0/1 no alarm/at least one device has one filter alarm
11 return_air_min READ d6 ui16 x/100 °C
12 return_air_max READ d6 ui16 x/100 °C
13 thermostat_on READ 1 fc4 ui16 0/1/2/3 idle,ventilator/heating/cooling/heating and cooling
14 defrost READ 1 fc4 ui16 0/1 no defrosting/at leas one device in in defrost mode