General parameter

General Modbus-parameter

Note


Documents

0 Daikin RTD-W Installationsanleitung

Device Description File



Profile

INDEX NAME DIRECTION REGISTER COUNT FUNCTION TYP CONVERTION ENUMS UNIT
1 setpoint_outlet_water_cooling_mode READ & WRITE 2 1 fc3/fc16 ui16 °C
2 operating_mode READ & WRITE 3 1 fc3/fc16 ui16 1|2 heizen/kühlen
3 modbus_on/off_room_heating/cooling READ & WRITE 4 1 fc3/fc16 ui16 0/1 aus/ein
4 setpoint_room_temperature READ & WRITE 5 1 fc3/fc16 ui16 °C
5 modbus_hot_water_warm_up READ & WRITE 6 1 fc3/fc16 ui16 0/1 aus/ein
6 start_hot_water_tank READ & WRITE 7 1 fc3/fc16 ui16 0/1 leerlauf/start
7 operating_mode_and_ on/off_control_source READ & WRITE 8 1 fc3/fc16 ui16 1|2|3 extern/lokal/bei anderung
8 whisper_mode READ & WRITE 9 1 fc3/fc16 ui16 0/1 deaktivieren/aktivieren
9 weather-dependent_setpoint_operation READ & WRITE 10 1 fc3/fc16 ui16 0/1 deaktivieren/aktivieren
10 P1P2_circuit_board_counter READ 20 3 fc4 ui16
11 group_error READ d10 ui16 0/1 kein fehler/fehler
14 average_outlet_water_temperature READ d10 ui16 x/100 °C
15 remco-room_temperature READ 50 1 fc4 ui16 x/100 °C
16 on/off_room_heating/cooling READ 70 3 fc4 ui16 0/1 aus/ein
17 circulation_pump_operation READ d16 ui16 0/1 aus/ein
18 compressor_mode READ d16 ui16 0/1 aus/ein
19 disinfection_mode READ 74 5 fc4 ui16 0/1 aus/beschädigt
20 lowering_mode READ d19 ui16 0/1 aus/beschädigt
21 defrost/start_up READ d19 ui16 0/1 aus/beschädigt
22 hot_water_heating READ d19 ui16 0/1 aus/beschädigt
23 hot_water_storage READ d19 ui16 0/1 nicht beschädigt/beschädigt
24 room_heating_on READ 10001 4 fc4 ui16 0/1 aus/ein
25 room_cooling_on READ fc4 ui16 0/1 aus/ein
26 hot_water-warm-up_disabled READ fc4 ui16 0/1 aus/ein
27 whisper_mode_activated READ fc4 ui16 0/1 aus/ein
28 setpoint_room_heating/cooling READ 10006 1 fc4 ui16 x/1000