0 Fujitsu General Limited UTY-VMSX Registerlist

Device Description File



Profile

INDEX NAME DIRECTION REGISTER COUNT FUNCTION TYP CONVERTION ENUMS UNIT
0 operation_mode READ 30054 2 fc4 ui16 1: auto, 2: cool, 3: dry, 4:heat, 5:fan
1 set_temperature_status READ 30056 2 fc4 ui16 temp =value/4 (0=0°C, 80=2°C)
2 air_flow_status READ 30057 2 fc4 ui16 1: auto, 2: quiet, 3: low, 4: med, 5: high, 6: med-low, 7: med-high
3 indoor_temperature READ 30058 2 fc4 ui16 temp =value/4 (0=0°C, 80=2°C)
4 vertical_air_direction READ & WRITE 40006 2 fc3/fc16 ui16 1: swing, 2: pos1, 3: pos2, 4: pos3, 5: pos4
5 horizontal_air_direction READ & WRITE 40007 2 fc3/fc16 ui16 1: swing, 2: pos1, 3: pos2, 4: pos3, 5: pos4, 6: pos5
6 operation_mode_setting READ & WRITE 40002 2 fc3/fc16 ui16 0: no change, 1: auto, 2: cool, 3: dry, 4:heat, 5:fan
7 operation_on_off_setting READ & WRITE 40003 2 fc3/fc16 ui16 0: no change, 1: stop, 2: operation
8 set_temperature_setting READ & WRITE 40004 2 fc3/fc16 ui16 bit0: change/nochange, bit1..bit7: value -> temp =value/4 (0=0°C, 80=2°C)
9 airflow_setting READ & WRITE 40005 2 fc3/fc16 ui16 0: no change, 1: auto, 2: quiet, 3: low, 4: med, 5: high, 6: med-low, 7: med-high
10 upper_limit_value_cool/dry READ & WRITE 40012 2 fc3/fc16 ui16 bit0: change/nochange, bit1..bit7: value -> temp =value/4 (0=0°C, 80=2°C)
11 lower_limit_value_cool/dry READ & WRITE 40013 2 fc3/fc16 ui16 bit0: change/nochange, bit1..bit7: value -> temp =value/4 (0=0°C, 80=2°C)
12 upper_limit_value_heat READ & WRITE 40014 2 fc3/fc16 ui16 bit0: change/nochange, bit1..bit7: value -> temp =value/4 (0=0°C, 80=2°C)
13 lower_limit_value_heat READ & WRITE 40015 2 fc3/fc16 ui16 bit0: change/nochange, bit1..bit7: value -> temp =value/4 (0=0°C, 80=2°C)
14 upper_limit_value_auto READ & WRITE 40016 2 fc3/fc16 ui16 bit0: change/nochange, bit1..bit7: value -> temp =value/4 (0=0°C, 80=2°C)
15 lower_limit_value_auto READ & WRITE 40017 2 fc3/fc16 ui16 bit0: change/nochange, bit1..bit7: value -> temp =value/4 (0=0°C, 80=2°C)