DEVICE DB Login

General parameter

General Modbus-parameter

Note


Documents

0 Meltem M-WRG-II ventilation Technische Handbuch
0 Meltem M-WRG-II-ventilation Installationanleitung

Device Description File



Profile

INDEX NAME DIRECTION REGISTER COUNT FUNCTION TYP CONVERTION ENUMS UNIT
0 error_report READ 41016 1 fc4 bool 0/1 0x00= ok, 0x01= error
1 frost_protection_function READ 41018 1 fc4 bool 0/1 0x00= inactive, 0x01= active
2 exhaust_air_temperature READ 41000 6 fc4 float32 °C
3 outdoor_air_temperature READ d2 float32 °C
4 extract_air_temperature READ d2 float32 °C
5 supply_air_temperature READ 41009 2 fc4 float32 °C
6 humid_exhaust_air READ 41006 2 fc4 ui16 %
7 humid_supply_air READ 41011 2 fc4 ui16 %
8 CO2_exhaust_air READ 41007 2 fc4 ui16 ppm
9 VOC_supply_air READ 41013 2 fc4 ui16 ppm
10 exhaust_air_ventilation_stage READ 41020 1 fc4 ui8 m³/h
11 supply_air_ventilation_stage READ 41021 1 fc4 ui8 m³/h
12 air_filter_change_indicator READ 41017 1 fc4 bool 0/1 0x00= not expired, 0x01= expired
13 time_until_air_filter_ change READ 41027 2 fc4 ui16 days
14 operating_hours_ventilation_unit READ 41030 4 fc4 ui32 h
15 operating_hours_ventilation_motors READ d14 ui32 h
16 rel_humidity_starting_point READ & WRITE 42000 1 fc3/fc16 ui8 step=1 %
17 min_ventilation_stage_humidity_control READ & WRITE 42001 1 fc3/fc16 ui8 step=10 %
18 max_ventilation_stage_humidity_control READ & WRITE 42002 1 fc3/fc16 ui8 step=10 %
19 CO2_starting_point READ & WRITE 42003 2 fc3/fc16 ui16 step=1 ppm
20 min_ventilation_stage_CO2_regulation READ & WRITE 42004 1 fc3/fc16 ui8 step=10 %
21 max_ventilation_stage_CO2_regulation READ & WRITE 42005 1 fc3/fc16 ui8 step=10 %
22 ventilation_stage_external_control_input READ & WRITE 42007 1 fc3/fc16 ui8 step=10 %
23 switch-on_delay_external_control_input READ & WRITE 42008 1 fc3/fc16 ui8 step=1 min
24 follow-up_time_external_control_input READ & WRITE 42009 1 fc3/fc16 ui8 step=1 min